Clean Electricity Regulations, SOR/2024-263

Section 36

Measuring devices — installation, maintenance and calibration

Cite as Clean Electricity Regulations, SOR/2024-263, s. 36 · current to July 24, 2025 · regulation last amended January 1, 2025

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

(1) A responsible person must install, maintain and calibrate all measuring devices, other than a CEMS, that are used for the purposes of these Regulations in accordance with the manufacturer’s instructions or any applicable generally recognized national or international industry standard. (2) The responsible person must calibrate each measuring device (a) at least once in every calendar year and at least five months after a previous calibration; or (b) at the minimum frequency recommended by the manufacturer. (3) The responsible person must use measuring devices that enable measurements to be made with an accuracy of (a) ± 3% in the case of any device used to measure a quantity of electricity; and (b) ± 5% in the case of any other device. (4) However, if a document incorporated by reference into these Regulations requires measurements that are more accurate than what is required by subsection (3), the responsible person must use a measuring device that enables measurements to be made with the degree of accuracy required by that document.
Read the Clean Electricity Regulations on the Justice Laws Website ↗

Made under Canadian Environmental Protection Act, 1999, S.C. 1999, c. 33.