Canada–Nova Scotia Offshore Area Petroleum Operations Framework Regulations, SOR/2024-26

Section 126

Emergency electrical power supply

Cite as Canada–Nova Scotia Offshore Area Petroleum Operations Framework Regulations, SOR/2024-26, s. 126 · current to September 21, 2026 · regulation last amended September 17, 2026

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

(1) An operator must ensure that an installation has an emergency electrical power supply that is independent of the main electrical power supply such that the following systems and equipment continue to function in the event of a failure of the main electrical power supply: (a) lights at (i) all embarkation and debarkation stations and evacuation points, (ii) all escape routes, temporary safe refuges, service corridors, accommodations area corridors, stairways, exits and personnel lift cars, (iii) all control centres, control stations and areas from which the communication system referred to in section 129 is controlled, (iv) spaces from which drilling or production equipment, including any equipment that is critical to that equipment’s operation, is controlled, (v) spaces where equipment that is related to the emergency shutdown system referred to in section 133 and to the power plants referred to in paragraph 122(4)(b) is located, (vi) areas where emergency response equipment is stored, and (vii) aircraft landing areas and the location of any obstacle to take-off and landing; (b) hazard detection systems, including the central monitoring system referred to in section 169 and the fire and gas detection system referred to in section 132; (c) emergency response and life-saving systems, including life-saving appliances that require electrical power; (d) the communication system referred to in section 129; (e) the emergency shutdown system referred to in section 133; (f) the lights and sound-signalling appliances referred to in section 127; (g) in the case of a floating platform, the pumps and powered watertight doors and hatches that are necessary to stabilize the installation, having regard to the failure modes and effects analysis referred to in subsection 144(5); (h) in the case of a column-stabilized mobile offshore platform, the ballast systems referred to in section 144; (i) the systems and equipment that are necessary to safely suspend at any time drilling or production that is in progress, including (i) blowout prevention systems, including the blowout preventer referred to in subsection 68(5), (ii) any disconnectable mooring system referred to in section 148, (iii) any disconnect system referred to in section 150, and (iv) pumping systems; and (j) any other system or equipment that requires electrical power and that is referred to in the operator’s safety plan referred to in section 9 or its contingency plan referred to in section 11. (2) If the emergency electrical power supply is a mechanically driven generator, the operator must ensure that (a) the installation is equipped with a transitional source of electrical power, unless the generator will automatically start and supply the necessary power in less than 45 seconds from the time the main electrical power supply fails; (b) the installation is equipped with a self-contained battery system that is designed, on failure or shutdown of both the main electrical power supply and the emergency electrical power supply, to automatically supply sufficient power to operate (i) for a period of at least one hour, the lights that are located in any emergency exit route, any escape route, any space where equipment incorporating an internal combustion engine, gas turbine, electric motor, generator, pump or compressor is found, any control centre and any emergency assembly room and at every launching station of life-saving appliances, (ii) for a period of at least one hour, the communication system referred to in section 129 and the general alarm system referred to in section 130, and (iii) for a period of at least four days, the lights and sound-signalling appliances referred to in section 127; and (c) the mechanically driven generator has redundancy in its starting capabilities and a dedicated fuel source. (3) The operator must ensure that the emergency electrical power supply together with any transitional source of electrical power and self-contained battery system with which the installation may be equipped are designed and maintained such that (a) they are able to provide the systems and equipment referred to in subsection (1) with an emergency power supply of sufficient capacity, taking into account starting currents and the transitory nature of electrical loads, and sufficient duration to ensure that the systems and equipment can function as intended and to allow for effective management of the installation during an emergency, including (i) to allow for the complete shutdown and evacuation of the installation, (ii) to facilitate emergency response and the safe escape, refuge and evacuation of persons or to maintain the integrity of the installation, (iii) to ensure sufficient power so that systems that must operate simultaneously can do so, (iv) in the case of a floating platform, to maintain the flotation and stability of the platform, and (v) to bring a well to a safe state and to maintain it in that state; (b) their capacity to provide power to essential systems is not compromised during their maintenance; (c) they have sufficient redundancy to ensure their reliability and, as far as is practicable, to ensure their functional and physical independence from other essential systems or, if that is not practicable, they are arranged so as not to adversely affect or be adversely affected by the operation of those systems; and (d) they are readily accessible. (4) The operator must ensure that the emergency electrical power supply, transitional source of electrical power and self-contained battery system referred to in subsection (3) are arranged — or are otherwise protected from mechanical damage and damage caused by fire, explosion and physical and environmental conditions to which they may be exposed — so that they remain capable of fulfilling their intended functions under all foreseeable operating conditions, including, in the case of a floating platform, under the static and dynamic angles of inclination referred to in subsection 136(7). (5) The operator must ensure that, in the event of a failure of the main electrical power supply, all control centres are alerted by means of an audible and visual signal that the installation is being powered by the emergency electrical power supply.
Read the Canada–Nova Scotia Offshore Area Petroleum Operations Framework Regulations on the Justice Laws Website ↗

Made under Canada–Nova Scotia Offshore Petroleum Resources Accord Implementation and Offshore Renewable Energy Management Act, S.C. 1988, c. 28.

Bills in Parliament that would change this section 0

No bill we hold would amend or repeal this section.