Exposure to hazardous energy, including as a result of the unexpected start-up of any equipment, machine, device or system or as a result of contact with or a failure of electrical equipment, is a prescribed risk for the purpose of paragraph 205.02(2)(a) of the Act and every occupational health and safety program must
(a) set out, for each piece of equipment, machine, device and system at the workplace that may present such a risk,
(i) the nomenclature by which it is to be identified, which must be consistent with any associated design documents,
(ii) detailed procedures for de-energizing it and isolating its energy source using an energy-isolating device at all possible locations, both local and remote, and
(iii) detailed procedures for verifying and testing that the de-energization and isolation are complete;
(b) set out detailed procedures for securing and removing lockout devices and for affixing tags or signs to those devices;
(c) set out the method by which persons in the vicinity of any equipment, machine, device or system are to be notified of its lockout;
(d) set out procedures for the orderly transfer of control of lockout devices between outgoing and incoming employees during shift or personnel changes;
(e) set out measures for ensuring that, before any equipment, machine, device or system that has been locked out is re-energized, all persons are clear of — and have been instructed to remain clear of — the area in which they would be at risk of exposure to hazardous energy;
(f) set out procedures for the inspection and testing of electrical equipment and circuits, including the selection of appropriate testing equipment, having regard to the electrical code to which the workplace is designed;
(g) set out procedures for maintaining the integrity of any electrical equipment’s insulation and its enclosure;
(h) set out procedures for all work involving hazardous energy, including in relation to
(i) the selection of appropriate tools,
(ii) the use of personal protective equipment and other protective devices, and
(iii) communication with persons in the vicinity of the location where the work is being carried out to ensure the safe coordination of the work with other activities;
(i) identify the limited approach boundaries and restricted approach boundaries that apply to all locations at the workplace where shock hazards exist;
(j) identify the arc flash boundary for every piece of electrical equipment at the workplace that gives rise to an arc flash hazard;
(k) address the number of persons, including electrical safety watchers, needed to safely carry out electrical work and the competencies those persons must meet;
(l) set out procedures for carrying out work involving multiple power systems, if applicable;
(m) set out procedures for responding to emergencies involving hazardous energy, including with respect to the use of emergency equipment; and
(n) address precautions to be taken with respect to battery rooms.