Regulations Limiting Carbon Dioxide Emissions from Natural Gas-fired Generation of Electricity, SOR/2018-261
Section 9
Measuring devices — installation, maintenance and calibration
Cite as Regulations Limiting Carbon Dioxide Emissions from Natural Gas-fired Generation of Electricity, SOR/2018-261, s. 9 · current to July 24, 2025 · regulation last amended January 1, 2019
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) A responsible person for a unit must install, maintain and calibrate a measuring device — other than a continuous emission monitoring system and a measuring device that is subject to the Electricity and Gas Inspection Act — that is used for the purposes of these Regulations in accordance with the manufacturer’s instructions or any applicable generally recognized national or international industry standard.
(2) The responsible person must calibrate each of the measuring devices at the greater of the following frequencies:
(a) at least once in every calendar year but at least five months after a previous calibration, and
(b) the minimum frequency recommended by the manufacturer.
(3) The responsible person must use measuring devices that enable measurements to be made with a degree of accuracy of ± 5%.
Read the Regulations Limiting Carbon Dioxide Emissions from Natural Gas-fired Generation of Electricity on the Justice Laws Website ↗
Made under Canadian Environmental Protection Act, 1999, S.C. 1999, c. 33.
Bills in Parliament that would change this section 0
No bill we hold would amend or repeal this section.