Regulations Limiting Carbon Dioxide Emissions from Natural Gas-fired Generation of Electricity, SOR/2018-261
Section 4
General
Cite as Regulations Limiting Carbon Dioxide Emissions from Natural Gas-fired Generation of Electricity, SOR/2018-261, s. 4 · current to July 24, 2025 · regulation last amended January 1, 2019
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) A responsible person for a unit must not emit from the unit an amount of CO2 from the combustion of fossil fuels in the unit, that is, during a calendar year, on average, greater than any of the following intensity limits, as applicable:
(a) 420 tonnes of CO2 emissions/GWh of energy produced
(i) in the case of boiler units, other than those referred to in subsection 3(4), and
(ii) in the case of combustion engine units that are equipped with at least one combustion engine that has a capacity of more than 150 MW; and
(b) 550 tonnes of CO2 emissions/GWh of energy produced in the case of combustion engine units that are equipped with combustion engines that have a capacity of 150 MW or less.
(2) It is prohibited for a responsible person for a boiler unit referred to in subsection 3(4) to emit from the boiler unit an amount of CO2, from the combustion of fossil fuels in the unit, that is, during a calendar year, on average, greater than 420 tonnes of CO2 emissions/GWh of energy produced, as applicable, beginning in
(a) the year after the unit’s end of useful life, if the initial performance test conducted under subsection 5(1) indicates a CO2 emissions intensity greater than 600 t/GWh;
(b) the sixth year after the unit’s end of useful life, if the initial performance test conducted under subsection 5(1) indicates a CO2 emissions intensity greater than 550 t/GWh and less than or equal to 600 t/GWh;
(c) the ninth year after the unit’s end of useful life, if the initial performance test conducted under subsection 5(1) indicates a CO2 emissions intensity greater than 480 t/GWh and less than or equal to 550 t/GWh; or
(d) the eleventh year after the unit’s end of useful life, if the initial performance test conducted under subsection 5(1) results in a CO2 emissions intensity less than or equal to 480 t/GWh.
(3) For the purposes of subsections (1) and (2),
(a) the quantity of energy produced in the calendar year must be determined in accordance with section 11; and
(b) the quantity of CO2 emissions produced in the calendar year must be determined in accordance with sections 12 to 18, as applicable.
(4) For the purposes of subsection (3), if, in the calendar year, one of the combustion engines of the unit is repaired or maintained and one or more replacement combustion engines are temporarily installed, the quantity of energy and CO2 emissions produced during the replacement period, to a maximum of 90 days per calendar year, are excluded from the calculation referred to in that paragraph.
(5) Despite subsection (1), a boiler unit that, in a calendar year, does not meet one of the conditions set out in subsection 3(1), is not subject to the emission intensity limit for that calendar year.
(6) Despite subsection (1), a combustion engine unit that, in a calendar year, does not meet one of the conditions set out in subsection 3(2), is not subject to the emission intensity limit for that calendar year.
Read the Regulations Limiting Carbon Dioxide Emissions from Natural Gas-fired Generation of Electricity on the Justice Laws Website ↗
Made under Canadian Environmental Protection Act, 1999, S.C. 1999, c. 33.
Bills in Parliament that would change this section 0
No bill we hold would amend or repeal this section.