Vessel Fire Safety Regulations, SOR/2017-14

Section 131

Cite as Vessel Fire Safety Regulations, SOR/2017-14, s. 131 · current to July 24, 2025 · regulation last amended November 23, 2022

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

In addition to the requirements of regulation 10.2.2, the following requirements must be met in respect of a vessel’s fire pumps: (a) if the vessel is fitted with two or more power-driven fire pumps, a non-return valve must be fitted to the discharge line of each pump to prevent water from backing through the pump when it is not operating; (b) a power-driven fire pump must be self-priming and fitted with pressure gauges on their suction and discharge sides; (c) a manual fire pump must be operable without the need for manual priming and must be capable of delivering a jet of water of at least 12 m from the nozzle; (d) a fire pump’s sea connection must have arrangements to prevent blockage of the connection’s inlet by ice, slush and debris; and (e) a fire pump must not have an impeller that can be damaged by heat from the pump or by the pump running dry.
Read the Vessel Fire Safety Regulations on the Justice Laws Website ↗

Made under Canada Shipping Act, 2001, S.C. 2001, c. 26.