Vessel Fire Safety Regulations, SOR/2017-14

Section 126

Cite as Vessel Fire Safety Regulations, SOR/2017-14, s. 126 · current to July 24, 2025 · regulation last amended November 23, 2022

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

(1) If the fire main is an integral part of a fixed deck foam fire-extinguishing system with monitors, the isolating valves required by regulation 10.2.1.4.1 must be fitted immediately forward of each monitor. (2) In addition to the isolating valves required by regulation 10.2.1.4.1, valves must be fitted to sections of the fire main that (a) are subject to freezing; (b) could be damaged because of a fire or explosion; or (c) might not be required when any other part of the fire main is used. (3) The valves required by subsection (2) must be (a) operable from positions that are readily accessible (b) protected from freezing, fire and explosions; and (c) clearly marked. (4) Every valve fitted to fire piping must be designed to open with a counter-clockwise rotation of the valve’s handle. (5) The requirements of regulation 10.2.1.4.4 apply in respect of combination carriers.
Read the Vessel Fire Safety Regulations on the Justice Laws Website ↗

Made under Canada Shipping Act, 2001, S.C. 2001, c. 26.