PCB Regulations, SOR/2008-273
Section 27
Inspection and maintenance of a PCB storage site
Cite as PCB Regulations, SOR/2008-273, s. 27 · current to June 14, 2026 · regulation last amended June 12, 2026
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
The owner or operator of a PCB storage site shall
(a) inspect all floors, curbing, sides, drains, drainage systems, weatherproof roofs and barriers, fences and walls of the PCB storage site, any fire alarm system, fire extinguishers and fire suppression system and all equipment containing PCBs, containers used for the storage of PCBs or products containing PCBs and materials for clean-up at the PCB storage site
(i) each month,
(ii) at intervals of more than one month, if the Minister, on the written request of the owner or operator, determines that it is not reasonably practicable to inspect the site each month, due to its remote location, or
(iii) at intervals of less than one month, if more frequent inspections are necessary for the safe operation of the site; and
(b) keep in good condition and, if damaged, immediately repair or replace the floors, curbing, sides, drains, drainage systems, weatherproof roofs or barriers, fences, walls, fire alarm system, fire extinguishers, fire suppression system, equipment containing PCBs and containers and immediately clean up any contaminated area.
Read the PCB Regulations on the Justice Laws Website ↗
Made under Canadian Environmental Protection Act, 1999, S.C. 1999, c. 33.