Storage Tank Systems for Petroleum Products and Allied Petroleum Products Regulations, SOR/2008-197
Section 24
Cite as Storage Tank Systems for Petroleum Products and Allied Petroleum Products Regulations, SOR/2008-197, s. 24 · current to September 1, 2025 · regulation last amended August 28, 2025
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
The piping precision leak detection test referred to in section 17 and paragraphs 23(1)(c) and 26(d) must
(a) be capable of detecting a leak rate of at least 0.38 L/h within a 24 hour period at a line pressure of 310 kPa with a probability of detection of 0.95 or greater and a probability of false alarm of 0.05 or less, accounting for variables such as vapour pockets, thermal expansion and contraction, static head pressure, temperature differential and piping compressibility; and
(b) be performed, using a documented and validated method, by an individual trained in the maintenance and use of the test equipment.
Read the Storage Tank Systems for Petroleum Products and Allied Petroleum Products Regulations on the Justice Laws Website ↗
Made under Canadian Environmental Protection Act, 1999, S.C. 1999, c. 33.
Bills in Parliament that would change this section 0
No bill we hold would amend or repeal this section.