Storage Tank Systems for Petroleum Products and Allied Petroleum Products Regulations, SOR/2008-197

Section 21

Cite as Storage Tank Systems for Petroleum Products and Allied Petroleum Products Regulations, SOR/2008-197, s. 21 · current to September 1, 2025 · regulation last amended August 28, 2025

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

The tank precision leak detection test referred to in section 16 and paragraphs 19(1)(c), 26(a) and 43(b) must (a) be capable of measuring the level of water in the tank to within 3 mm with a probability of 0.95 or greater; (b) if a volumetric method is used, be capable of measuring the level of liquid in the tank to within 3 mm with a probability of 0.99 or greater; (c) be capable of detecting a leak rate of at least 0.38 L/h within a 24 hour period with a probability of detection of 0.95 or greater and a probability of false alarm of 0.05 or less, accounting for variables such as vapour pockets, thermal expansion and contraction, evaporation and condensation, temperature stratification, groundwater level and tank deformation; and (d) be performed, using a documented and validated method, by an individual trained in the maintenance and use of the test equipment.
Read the Storage Tank Systems for Petroleum Products and Allied Petroleum Products Regulations on the Justice Laws Website ↗

Made under Canadian Environmental Protection Act, 1999, S.C. 1999, c. 33.

Bills in Parliament that would change this section 0

No bill we hold would amend or repeal this section.