Storage Tank Systems for Petroleum Products and Allied Petroleum Products Regulations, SOR/2008-197

Section 17

Cite as Storage Tank Systems for Petroleum Products and Allied Petroleum Products Regulations, SOR/2008-197, s. 17 · current to September 1, 2025 · regulation last amended August 28, 2025

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

(1) The owner or operator of a storage tank system installed before June 12, 2008 that has single-walled underground piping must test that piping using a piping precision leak detection test in accordance with section 24 within two years after June 12, 2008 and after that test they must (a) immediately (i) use continuous external underground pipe leak monitoring, (ii) use automatic tank gauging in accordance with section 18, or (iii) use continuous in-tank leak detection in accordance with section 20; or (b) annually perform a piping precision leak detection test in accordance with section 24. (2) The continuous external underground pipe leak monitoring must (a) be carried out using a sensor cable system designed for installation adjacent to the piping and within the same pipe trench; (b) be capable of detecting a leak rate of at least 0.38 L/h within 96 hours after the onset of the leak at the lowest expected soil temperature at the site where the sensor cable system is installed; (c) be capable of locating the leak with an accuracy of ± 1 m; (d) be capable of continuously monitoring sensor cable system integrity; and (e) have an alarm located at a place of work where it can be readily heard and seen.
Read the Storage Tank Systems for Petroleum Products and Allied Petroleum Products Regulations on the Justice Laws Website ↗

Made under Canadian Environmental Protection Act, 1999, S.C. 1999, c. 33.

Bills in Parliament that would change this section 0

No bill we hold would amend or repeal this section.