Canadian Energy Regulator Processing Plant Regulations, SOR/2003-39
Section 19
Cite as Canadian Energy Regulator Processing Plant Regulations, SOR/2003-39, s. 19 · current to July 24, 2025 · regulation last amended March 16, 2020
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
A company shall ensure that equipment that has a source of ignition with which gas at explosive levels may come into contact is not located in the same building as any process vessel or other source of flammable vapour, unless
(a) air intake flues are located outside the building in an area where gas is unlikely to be present;
(b) relief valves, burst plates and other sources of flammable fluids are vented from the building or discharged to a flare header, or other location that is environmentally safe;
(c) a specific risk analysis is conducted to determine what active, reactive or passive safety devices should be installed on that equipment and the company installs those devices; and
(d) the building is cross-ventilated.
Read the Canadian Energy Regulator Processing Plant Regulations on the Justice Laws Website ↗
Made under N-7.