Joint Use of Poles Regulations, C.R.C., c. 1185
Section 9
Cite as Joint Use of Poles Regulations, C.R.C., c. 1185, s. 9 · current to July 24, 2025 · regulation last amended June 18, 2015
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) Adequate and safe clearances shall be maintained between supply and communication conductors on the same poles, such clearances being not less than those recited as follows:
(a) for supply circuit voltages of 0 to 8,000, a vertical clearance of 40 inches; and
(b) for supply circuit voltages over 8,000, a vertical clearance of 60 inches.
(2) Metal sheathed supply cables of any voltage may be erected with clearances of 40 inches if the sheaths of the cables are permanently and effectively grounded.
(3) Appurtenances associated with supply and communication conductors shall have the same clearances as the conductors, except that cross-arm braces are not considered to be appurtenances if these braces are separated by at least one inch from metal parts of other appurtenances; span wires for trolley conductors and lamp brackets are excepted from these requirements.
Read the Joint Use of Poles Regulations on the Justice Laws Website ↗
Made under Railway Safety Act, R.S.C. 1985, c. 32 (4th Supp.).