Liquefied Petroleum Gases Bulk Storage Regulations, C.R.C., c. 1152

Section 76

Cite as Liquefied Petroleum Gases Bulk Storage Regulations, C.R.C., c. 1152, s. 76 · current to July 24, 2025 · regulation last amended June 18, 2015

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

(1) All liquefied petroleum gases shall be effectively odourized by an approved agent of such character as positively indicates, by distinct odour, the presence of gas down to concentrations in air of not over one-fifth the lower limit of flammability. For propane the lower limit of flammability is 2.37 per cent. (2) Exemption from the requirements of this section may be granted if it is established to the satisfaction of the Commission that the odourant will be harmful in subsequent processing or use of the gas. (3) The requirements of subsection (1) shall be deemed to be complied with if 1 pound of Ethyl Mercaptan, 1 pound of Thiophane, or 1.4 pounds of Amyl Mercaptan per 10,000 gallons of liquefied petroleum gas is used. The listing of odourants in this section is not intended to exclude the use of other odourants which meet the requirements of subsection (1).
Read the Liquefied Petroleum Gases Bulk Storage Regulations on the Justice Laws Website ↗

Made under Railway Safety Act, R.S.C. 1985, c. 32 (4th Supp.).