Liquefied Petroleum Gases Bulk Storage Regulations, C.R.C., c. 1152

Section 71

Cite as Liquefied Petroleum Gases Bulk Storage Regulations, C.R.C., c. 1152, s. 71 · current to July 24, 2025 · regulation last amended June 18, 2015

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

(1) Water, dry powder, carbon dioxide, or other fire extinguishers suitable for liquefied petroleum gas fires shall be available on installations with storage capacities exceeding 2,000 Imperial gallons. At least one fire extinguisher shall be kept on the outside premises. (2) Each storage area with a capacity exceeding 2,000 Imperial gallons should be protected by at least one standard fire hydrant so located that a 2 1/2-inch hose stream may be used for controlling a fire on the site or cooling a tank in case of adjacent fires. Consultation with the local fire authority on these matters is recommended.
Read the Liquefied Petroleum Gases Bulk Storage Regulations on the Justice Laws Website ↗

Made under Railway Safety Act, R.S.C. 1985, c. 32 (4th Supp.).

Bills in Parliament that would change this section 0

No bill we hold would amend or repeal this section.