Liquefied Petroleum Gases Bulk Storage Regulations, C.R.C., c. 1152
Section 46
Cite as Liquefied Petroleum Gases Bulk Storage Regulations, C.R.C., c. 1152, s. 46 · current to July 24, 2025 · regulation last amended June 18, 2015
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) The use of stationary internal combustion engines for the operation of liquefied petroleum gas pumps, compressors or vapourizers is not recommended, but if necessary, the installation shall be in accordance with subsections (2), (3), (5), (6) and (7).
(2) If housed, an internal combustion engine shall be isolated from the pump or compressor by fireproof and vapourproof walls.
(3) Except for the frame, the building shall be constructed of non-combustible or fire restraint materials.
(4) The spark plugs and ignition system should be shielded and the engine equipped with a spark arrestor muffler.
(5) The entire system shall be maintained in good operating condition at all times.
(6) The exhaust shall terminate outside the building.
(7) The building shall be cross ventilated near the floor level with permanently open louvers.NOTE: Electric motors used for the operation of liquefied petroleum gas pumps, compressors or vapourizers shall be explosion proof, as prescribed in section 69.
Read the Liquefied Petroleum Gases Bulk Storage Regulations on the Justice Laws Website ↗
Made under Railway Safety Act, R.S.C. 1985, c. 32 (4th Supp.).
Bills in Parliament that would change this section 0
No bill we hold would amend or repeal this section.