Liquefied Petroleum Gases Bulk Storage Regulations, C.R.C., c. 1152
Section 38
Cite as Liquefied Petroleum Gases Bulk Storage Regulations, C.R.C., c. 1152, s. 38 · current to July 24, 2025 · regulation last amended June 18, 2015
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) All shut-off valves, throttling valves, gauges, fittings and accessory equipment shall be of a type suitable for liquefied petroleum gas service, and designed for not less than the maximum working pressure to which they will be subjected, except that the rated working pressure of valves, fittings, etc., subject to container pressure shall not be less than 250 psig.
(2) All valves, gauges, fittings and accessory equipment mentioned in subsection (1) shall be permanently marked or labelled with the “maximum working pressure” and “L.P.G.”; e.g. “250L.P.G.”.
(3) Cast iron pipe, valves and fitting are prohibited in piping carrying liquefied petroleum gas in the liquid phase or on liquefied petroleum gas containers and their connections.