Liquefied Petroleum Gases Bulk Storage Regulations, C.R.C., c. 1152
Section 34
Cite as Liquefied Petroleum Gases Bulk Storage Regulations, C.R.C., c. 1152, s. 34 · current to July 24, 2025 · regulation last amended June 18, 2015
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) Pipelines of 1/2 inch nominal diameter or under shall be wrought iron, steel, brass or copper pipe, or seamless copper, brass, steel or aluminium tubing. Copper tubing may be of the standard grade K or L or equivalent and shall have a minimum wall thickness of 0.032 inch. Aluminium tubing shall not be used in exterior locations or where it will come in contact with masonry or plaster walls or insulations.
(2) All piping and fittings over 1/2 inch nominal diameter shall be made of steel.
(3) Pipe joints may be screwed, flanged, welded, soldered or brazed with a material having a melting point exceeding 1,000°F. Joints on seamless copper, brass, steel or nonferrous gas tubing shall be made by means of approved gas tubing fittings, soldered or brazed with a material having a melting point exceeding 1,000°F. Welded joints or welding flanges are recommended for container connections exceeding 2 inches in diameter.
(4) Welding may only be done by a qualified welder recognized as such by the Boiler and Pressure Vessel Inspection Branch of the provincial government concerned.
(5) For working pressures of 125 psig or less, pipe and pipe fittings and tubing shall be designed for a pressure of at least 125 psig, and for working pressures above 125 psig, they shall be designed for the maximum pressure to which they may be subjected or 250 psig, whichever is the greater.
(6) For pressures of 250 psig or greater, extra heavy pipe and fittings shall be used for threaded piping. Tubing shall be of heavy walled seamless construction.
(7) The bursting strength of any pipe or tubing and fittings shall be not less than four times the design pressure of the tank to which they are connected and not less than four times that pressure to which in any instance they may be subjected in service by the action of a pump or other device.
Read the Liquefied Petroleum Gases Bulk Storage Regulations on the Justice Laws Website ↗
Made under Railway Safety Act, R.S.C. 1985, c. 32 (4th Supp.).
Bills in Parliament that would change this section 0
No bill we hold would amend or repeal this section.