Liquefied Petroleum Gases Bulk Storage Regulations, C.R.C., c. 1152

Section 28

Cite as Liquefied Petroleum Gases Bulk Storage Regulations, C.R.C., c. 1152, s. 28 · current to July 24, 2025 · regulation last amended June 18, 2015

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

Each storage tank exceeding 1,000 Imperial gallons water capacity shall be electrically grounded for protection against static electricity and lightning, as prescribed in National Fire Protection Association Pamphlet No. 77. The resistance to electrical discharge to ground should be as low as possible and preferably not more than 6 ohms.
Read the Liquefied Petroleum Gases Bulk Storage Regulations on the Justice Laws Website ↗

Made under Railway Safety Act, R.S.C. 1985, c. 32 (4th Supp.).