Flammable Liquids Bulk Storage Regulations, C.R.C., c. 1148
Section 41
Cite as Flammable Liquids Bulk Storage Regulations, C.R.C., c. 1148, s. 41 · current to July 24, 2025 · regulation last amended June 18, 2015
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) Stationary internal combustion engines or non-explosion proof motors should not be used for the operation of Class I flammable liquid pumps. However, when the use of such engines or motors is necessary, they shall be installed in accordance with the requirements of this section.
(2) Internal combustion engines or non-explosion proof motors, if housed, shall be isolated from the pump by a non-combustible and vapour-proof wall. Where shafts pierce the dividing wall, vapour-proof packing glands shall be installed.
(3) The spark plugs and ignition system of an internal combustion engine shall be shielded and the engine shall be equipped with a spark arrestor muffler.
(4) The engine exhaust shall terminate outside the building.
(5) The fuel storage tank for an internal combustion engine shall be located outside the building.
(6) The air intake to the carburetor of an internal combustion engine shall be located at least 18 inches above the pumphouse floor.
(7) The entire system of an internal combustion engine or of a non-explosion proof motor shall be maintained in good operating condition at all times.
(8) The main control switch for a non-explosion proof electric motor or the fuel shut-off valve or spark grounding device for an internal combustion engine shall be so located that the motor or engine may be stopped quickly in an emergency.
Read the Flammable Liquids Bulk Storage Regulations on the Justice Laws Website ↗
Made under Railway Safety Act, R.S.C. 1985, c. 32 (4th Supp.).