Flammable Liquids Bulk Storage Regulations, C.R.C., c. 1148
Section 39
Cite as Flammable Liquids Bulk Storage Regulations, C.R.C., c. 1148, s. 39 · current to July 24, 2025 · regulation last amended June 18, 2015
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) If the ground resistance of a Class I flammable liquid piping system exceeds 15 ohms, ground rods or other grounding devices shall be used.
(2) All grounded pipelines for Class I flammable liquids shall be bonded at the joints with one No. 4 or two No. 6 A.W.G. electrical connections if flow to ground is interrupted by a gasket, joint compound or other non-conductive barrier.
Read the Flammable Liquids Bulk Storage Regulations on the Justice Laws Website ↗
Made under Railway Safety Act, R.S.C. 1985, c. 32 (4th Supp.).