Flammable Liquids Bulk Storage Regulations, C.R.C., c. 1148
Section 37
Cite as Flammable Liquids Bulk Storage Regulations, C.R.C., c. 1148, s. 37 · current to July 24, 2025 · regulation last amended June 18, 2015
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) Pipelines running parallel to a track, except those between adjacent loading or unloading racks, shall not be closer than 10 feet to the gauge side of the nearest rail of that track and shall comply with subsection (2).
(2) Except as provided in section 38, pipelines on the railway right-of-way and within 20 feet of a track, except pipelines between adjacent loading or unloading racks, shall be laid not less than three feet below ground, or be enclosed in a reinforced concrete or steel trench with a recessed removable cover flush with the ground, or be carried on an overhead pipe bridge with a clearance above ground of not less than 13 feet, or be enclosed by a suitable chain link or similar fence.
Read the Flammable Liquids Bulk Storage Regulations on the Justice Laws Website ↗
Made under Railway Safety Act, R.S.C. 1985, c. 32 (4th Supp.).
Bills in Parliament that would change this section 0
No bill we hold would amend or repeal this section.