Flammable Liquids Bulk Storage Regulations, C.R.C., c. 1148

Section 20

Cite as Flammable Liquids Bulk Storage Regulations, C.R.C., c. 1148, s. 20 · current to July 24, 2025 · regulation last amended June 18, 2015

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

(1) Vertical above ground storage tanks shall be installed on non-combustible foundations of strength adequate to permanently support the tank in a true vertical position. The bottom of the tank shall be suitably protected against corrosion. (2) Horizontal above ground storage tanks shall be installed on non-combustible foundations of strength adequate to permanently support the tank in a true horizontal position. (3) Steel foundations exceeding 18 inches in height at the lowest point for above ground storage tanks with a capacity in excess of 3,000 Imperial gallons shall be made fireproof with a material that has a fire resistance rating of not less than two hours. (4) Below ground storage tanks shall be set on a firm foundation surrounded with soft earth or sand well tamped in place. Ashes or any other corrosive material shall not be used to cover storage tanks. (5) Except as provided in subsection (6) and in subsection (7), underground storage tanks shall be covered with a minimum of two feet of earth or with not less than one foot of earth, on top of which shall be placed a slab of reinforced concrete not less than four inches in thickness. (6) If below ground storage tanks may be subjected to vehicular traffic, they shall be protected against damage with at least three feet of earth cover or 18 inches of well tamped earth plus either six inches of reinforced concrete or eight inches of asphaltic concrete that shall extend at least 12 inches horizontally beyond the storage tank extremities in all directions. (7) Notwithstanding subsection (5), below ground storage tanks that are not entirely buried shall be covered with earth to a minimum depth of two feet with a slope on all sides not less than 1 1/2 feet horizontally to one foot vertically.
Read the Flammable Liquids Bulk Storage Regulations on the Justice Laws Website ↗

Made under Railway Safety Act, R.S.C. 1985, c. 32 (4th Supp.).

Bills in Parliament that would change this section 0

No bill we hold would amend or repeal this section.