Flammable Liquids Bulk Storage Regulations, C.R.C., c. 1148

Section 17

Cite as Flammable Liquids Bulk Storage Regulations, C.R.C., c. 1148, s. 17 · current to July 24, 2025 · regulation last amended June 18, 2015

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

(1) All pumphouses and outdoor pumps that are driven by non-explosion proof motors or internal combustion engines shall be located not less than 10 feet from any storage tank, loading or unloading rack or terminal, building or any other enclosure. (2) Except as provided in subsections (3) and (4), outdoor pumps driven by motors marked or labelled Class I, Division I, Group D, and wired in accordance with the Canadian Electrical Code for Class I, Division I, Group D, hazardous locations may be located anywhere on the installation site. (3) The installation of pumps or motors under a storage tank or in a warehouse or other building where flammable liquids are stored or handled or in buildings attached thereto is prohibited. (4) The distances of a pumphouse or an outdoor pump used for Class I flammable liquids from a refuse burner, furnace, forge, welding operation or similar source of ignition shall not be less than 50 feet and when practicable, such distance should be greater than 50 feet.