The notes or legend on the drawing shall include the following information:
(a) evidence that the Provincial Fire Marshal or other local fire authority having jurisdiction in the surrounding area has no objection to the proposed installation; this evidence may take the form of a plan signature by the authority concerned or of a letter addressed to the owning or operating company by such authority;
(b) a statement that the design and construction of the storage tanks will be in accordance with the requirements of subsection 21(1);
(c) size, contents and capacity in Imperial gallons of all storage tanks;
(d) type, size and construction of pumphouse, warehouse and any other building or enclosure on the installation site;
(e) type and size of motive power to be used for pumping equipment;
(f) type and size of heating unit if warehouse, office building, or any other enclosure is heated;
(g) indicate whether the track or tracks serving the installation are team tracks or private tracks; and
(h) location of installation by reference to the railway, subdivision, mileage and nearest town or city.